Mehdi Esmaieli
Condition assessment criteria evaluation of asymmetric aged and fully aged silicone rubber insulators based on leakage current harmonics
Esmaieli, Mehdi; Khodsuz, Masume; Nouri, Hassan
Abstract
The leakage current characteristic monitoring of transmission line insulators is considered a worthy technique for insulator state prediction. In this paper, the harmonic analysis of leakage current signals has been performed to analyze the composite insulator condition. Experimental studies of asymmetrically aged, fully aged, and virgin insulators have been conducted. The effects of different aging types, pollution, and humidity on leakage current components, such as harmonics and the phase differences with the applied voltage, have been investigated. The analysis of the results shows that the effect of asymmetric aging on leakage current components is non-linear, and this non-linearity increases with the degree of pollution. Also, the type of insulator aging can be determined by the ratio of the third- and fifth-order leakage current harmonics. For instance, the classification of insulators into virgin, asymmetrically aged, and fully aged can be determined by examining the corresponding value ranges of 0–0.5, 0.5–0.9, and>0.9, respectively. Similarly, the phase difference values of<15% and those>15% indicate the clean and polluted operating conditions individually.
Citation
Esmaieli, M., Khodsuz, M., & Nouri, H. (in press). Condition assessment criteria evaluation of asymmetric aged and fully aged silicone rubber insulators based on leakage current harmonics. IET Science Measurement and Technology, https://doi.org/10.1049/smt2.12176
Journal Article Type | Article |
---|---|
Acceptance Date | Dec 19, 2023 |
Online Publication Date | Dec 28, 2023 |
Deposit Date | Jan 5, 2024 |
Publicly Available Date | Jan 11, 2024 |
Journal | IET Science, Measurement and Technology |
Print ISSN | 1751-8822 |
Electronic ISSN | 1751-8830 |
Publisher | Institution of Engineering and Technology (IET) |
Peer Reviewed | Peer Reviewed |
DOI | https://doi.org/10.1049/smt2.12176 |
Keywords | condition monitoring, insulator contamination, insulators, ageing |
Public URL | https://uwe-repository.worktribe.com/output/11543760 |
Files
Condition assessment criteria evaluation of asymmetric aged and fully aged silicone rubber insulators based on leakage current harmonics
(3.6 Mb)
PDF
Licence
http://creativecommons.org/licenses/by/4.0/
Publisher Licence URL
http://creativecommons.org/licenses/by/4.0/
You might also like
ANSYS investigation of solar photovoltaic temperature distribution for improved efficiency
(2023)
Journal Article
Uncovering gas insulated substation transient behaviours using the equivalent cable model
(2023)
Journal Article
Downloadable Citations
About UWE Bristol Research Repository
Administrator e-mail: repository@uwe.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2024
Advanced Search