Skip to main content

Research Repository

Advanced Search

Time-based fault location method for LVdistributionsystems

Alamuti, Mohsen Mohammadi; Nouri, Hassan; Mohammadi, Mohsen; Montakhab, Mohammad

Time-based fault location method for LVdistributionsystems Thumbnail


Authors

Mohsen Mohammadi Alamuti

Profile image of Hassan Nouri

Hassan Nouri Hassan.Nouri@uwe.ac.uk
Reader in Electrical Power and Energy

Mohsen Mohammadi

Mohammad Montakhab



Abstract

© 2015, Springer-Verlag Berlin Heidelberg. Due to the utilization of fundamental frequency, current impedance-based fault location methods are able to locate only permanent and linear faults. The duration of the arc in low and medium voltage systems can be as short as a quarter of a cycle. This period, which is normal for intermittent faults, is insufficient for fundamental frequency-based fault location algorithms. Therefore, available methods are not applicable for intermittent arcing fault location. In this paper, the time-based method previously proposed by the authors has been developed to locate short duration faults in LV distribution systems. The advantage of the proposed method over available methods is its capability for locating faults using fewer samples, which enable the user to locate both arcing faults as well as normal faults in the network. The main characteristics of an arcing fault, i.e., non-linearity and short duration, have been addressed in the proposed algorithms methodology. Various characteristics of a LV distribution system (i.e., heterogeneity, unbalanced load and line, etc.) have been taken into account in the current enhanced algorithm. The validity of the devised algorithm is studied within PSCAD-EMTDC environment and the obtained results show a good accuracy.

Journal Article Type Article
Acceptance Date Nov 1, 2015
Publication Date Mar 1, 2016
Deposit Date Jan 6, 2016
Publicly Available Date Dec 9, 2016
Journal Electrical Engineering
Print ISSN 0948-7921
Electronic ISSN 1432-0487
Publisher Springer Verlag
Peer Reviewed Peer Reviewed
Volume 98
Issue 1
Pages 87-96
DOI https://doi.org/10.1007/s00202-015-0346-1
Keywords arcing fault location, single end, LV distribution feeder
Public URL https://uwe-repository.worktribe.com/output/913590
Publisher URL http://dx.doi.org/10.1007/s00202-015-0346-1
Related Public URLs http://people.uwe.ac.uk/Pages/person.aspx?accountname=campus%5Ch-nouri
Contract Date Dec 9, 2016