Muresan Alexandru
Mitigation of transient ground potential rise in gas insulated substations during very fast transient overvoltage
Alexandru, Muresan; Czumbil, Levente; Polycarpou, Alexis; Nouri, Hassan; Andolfato, Roberto; Micu, Dan D
Authors
Levente Czumbil
Alexis Polycarpou
Hassan Nouri Hassan.Nouri@uwe.ac.uk
Reader in Electrical Power and Energy
Roberto Andolfato
Dan D Micu
Abstract
This paper is focused on the assessment and mitigation of the transient response of a Gas Insulated Substation's (GIS) grounding grid to the fault due to voltage breakdown using the Partial Element Equivalent Circuit (PEEC) numerical approach. The adopted analysis methodology considers the magnetic induction by quantifying the electromagnetic couplings generated within the metallic components contained by the GIS configuration. The Transient Ground Potential Rise (TGPR) and transient current are computed and analyzed at several locations inside of GIS housing. With the aid of 3D graphical representation, the maximum amplitudes of the TGPR across the substation are illustrated. The mitigation efforts are considerably optimized by assuming the grounding grid sub-system is responsible for high frequency fault energy clearance based on identification method. By adopting several simplifications of the earthing system during the computational process, from a step-by-step analysis, it has been discovered that the grid located beneath the GIS enclosure will mostly attenuate the TGPR across the GIS building. Based on the aforementioned findings a successful mitigation technique is implemented.
Journal Article Type | Article |
---|---|
Acceptance Date | Feb 4, 2022 |
Online Publication Date | Feb 5, 2022 |
Publication Date | Jun 2, 2022 |
Deposit Date | Feb 7, 2022 |
Publicly Available Date | Feb 6, 2023 |
Journal | Electric Power Systems Research |
Print ISSN | 0378-7796 |
Publisher | Elsevier |
Peer Reviewed | Peer Reviewed |
Volume | 207 |
Article Number | 107824 |
DOI | https://doi.org/10.1016/j.epsr.2022.107824 |
Public URL | https://uwe-repository.worktribe.com/output/9003279 |
Files
Mitigation of transient ground potential rise in gas insulated substations during very fast transient overvoltage
(2.2 Mb)
PDF
Licence
http://creativecommons.org/licenses/by-nc-nd/4.0/
Publisher Licence URL
http://creativecommons.org/licenses/by-nc-nd/4.0/
Copyright Statement
This is the author's accepted manuscript. The published version is available: https://doi.org/10.1016/j.epsr.2022.107824
You might also like
A fast fault classification technique for power systems
(2014)
Journal Article
Component model effect on fast-front overvoltages in gas insulated substations
(2015)
Presentation / Conference Contribution
Restructuration of distribution power system using Genetics Algorithms
(2015)
Presentation / Conference Contribution
Downloadable Citations
About UWE Bristol Research Repository
Administrator e-mail: repository@uwe.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2025
Advanced Search